technical parameters of switchgear
item | unit | data | |||
rated voltage rated frequency rated current of circuit breaker rated current of switchgear rated peak withstand current (4s) rated peak withstand current (peak) rated short-circuit breaking current rated short-circuit making current (peak) |
kv hz a a ka ka ka ka |
3.6,7.2,12 50 630,1250,1600,2000,2500,3150,4000 630,1250,1600,2000,2500,3150,4000 16,20,25,31.5,40,50,63 40,50,63,80,100,125,160 16,20,25,31.5,40,50,63 40,50,63,80,100,125,160 |
|||
rated insulation level |
1min power frequency withstand voltage lightning impulse withstand voltage |
kv kv |
24 40 |
32 60 |
42 75 |
protection class | the shell is ip4x, and it is ip2x when the compartment door and circuit breaker chamber door are opened |
technical parameters of vd4 and vs1-12 vacuum circuit breaker
item | unit | data | |||
rated voltage rated frequency rated current of circuit breaker rated peak withstand current (4s) rated peak withstand current (peak) rated short-circuit breaking current rated short-circuit making current (peak) |
kv hz a a ka ka ka ka |
3.6,7.2,12 50 630,1250,1600,2000,2500,3150,4000 16,20,25,31.5,40,50,63 40,50,63,80,100,125,160 16,20,25,31.5,40,50,63 40,50,63,80,100,125,160 |
|||
rated insulation level | 1min power frequency withstand |
kv kv |
42 75 |
||
rated operating sequence rated short-circuit current breaking times mechanical life |
times times |
o-0.3s-co-180s-co 50 2000 |
item | unit | data | |||
clearance between open contacts overtravel phase-to-phase central distance closing contact bounce time three-phase opening asynchrony |
mm mm mm ms ms |
11±1 4±0.5 210±0.5,250±0.5,275±0.5 ≤2 ≤2 |
|||
breaking time at operating voltage of |
max rating min |
ms ms |
≤50 ≤50 ≤60 |
||
closing time average closing speed average closing speed conductive circuit resistance contact pressure |
ms m/s m/s μω n |
≤100 0.9-1.2 0.6-0.8 ≤40 3200±100 |
item | unit | value | |
rated operating voltage | closing coil | v | dc220,110 |
closing coil | v | dc220,110 | |
coil power | closing coil | w | 245 |
closing coil | w | 245 | |
power of energy-storage motor rated voltage of energy-storage motor energy-storage time |
w v s |
50 dc220,110 ≤10 |
item | unit | parameter |
rated voltage rated frequency rated current rated short-circuit breaking current rated short-circuit making current rated peak withstand current rated short-time withstand current rated short-circuit duration rated breaking current of single capacitor bank rated breaking current of back-to-back capacitor bank power frequency withstand voltage lightning impulse withstand voltage rated short-circuit current breaking times mechanical life |
kv hz a ka ka ka ka s a a kv kv times times |
12 50 1250 31.5 80 80 31.5 4 630 400 42 75 50 1000 |
rated operating sequence | o-0.3s-co-180s-co | |
opening time closing time control voltage power of closing coil power of opening coil |
ms ms v va va |